FLUKE EARTH GROUND TESTER 1621

  • bvseo_sdk, net_sdk, 2.2.0.2
  • getAggregateRating, method:CLOUD, 297ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
FLUKE INSTRUMENTS 1621
UOM: PC
Price w/GST:
$1,690.60


Easily capture values with single-button operation
3-pole Fall-of-Potential earth testing for basic measurements
2-pole resistance measurements for added versatility
Ensure accurate measurements with automatic ‘noise’ voltage detection
Hazardous voltage warning offers increased user protection
Clearly read and record data with a large, backlit display
Rugged holster and design for tough work environments
Portable size allows for easy transportation
Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting
600 V Cat II
Maximum deviations E1Influence factor Position
  E1Deviation influence 0%
  E2Influence factor Supply voltage
  E2Deviation influence 0%
  E3Influence factor Temperature E3
  E3Deviation influence 2.30%
  E4Influence factor Serial interference voltage (20 V)
  E4Deviation influence 0.60%
  E5Influence factor Probe- and auxiliary probe resistance
  E5Deviation influence 10%
Test voltage 3.7 kV  
Protection type IP 40; IEC/EN 60529  
Electromagnetic compatibility Emission IEC/EN 61326 Class B
  Immunity IEC/EN 61326 Annex C
RE Resistance measurement Measuring method Current-voltage measurement with improved cross-talk attenuation, no compensation of measuring lead resistance, with probe (3-pole) or without probe (2-pole), as per IEC/EN 61557–5
  Open circuit voltage 23 to 24 V AC
  Short circuit current > 50 mA AC
  Measuring frequency 128 Hz
  Maximum permissible overload 250 Veff
Measuring time 8 seconds (average from when START is pressed)
Limit input Tester retains set value even if instrument is turned off (assuming battery power supply is sufficient)
Automatic changeover of resolution RH < 7 kΩ
  Resolution 0.01 Ω
  RH < 50 kΩ
  Resolution 0.1 Ω
  RH > 50 kΩ
  Resolution 1 Ω
Interference voltage display DC + AC Vmax 30 Veff
  Common mode rejection > 80 dB at 50 Hz and 60 Hz
  Ri 680 kΩ
  Measuring uncertainty < 10% for pure AC and DC signals